 2.3
External wiring
Note 1: Please isolate analog input and other power wiring.
http://www.delta.com.tw/products/plc.asp
voltage input -10V~+10V
CH1 *5
DVP-EH
1
DVP04AD-H Analog Input Module
Instruction Sheet
WARNING
shielding cable*1 current input -20mA~+20mA
V+ I+ COM FG
104.7K 250 104.7K AG 104.7K 250 104.7K AG
CH1
Note 2: If connect to current signal, please short out between V+ and I+ terminals. Note 3: If noise is significant, please connect FG to ground. Note 4: Please connect terminal of power
CH4 *2
shielding cable*1 *3 terminal of power module *4 System Grounding Class 3 Grouning (100 or less)
V+ I+ COM FG
CH4
Please carefully read this instruction thoroughly prior to use the DVP04AD-H. The DC input power must be OFF before any maintenance. This is an OPEN-TYPE built-in DVP04AD-H, and the DVP04AD-H is certified to meet the safety requirements of IEC 61131-2 (UL 508) when installed in the enclosure to prevent high temperature, high humidity, exceessive vibration, corrosive gases, liquids, airbome dust or metallic particles. Also, it is equipped with protective methods such as some special tool or key to open the enclosure, in order to prevent the hazard to users and the damage to the DVP04AD-H. Do not connect the AC power to any of the input/output terminals, or it may damage the DVP04AD-H. Make sure that all the wiring is well conducted prior to power on. Do not touch the internal circuit for at least 1 minute after the power OFF. Make sure that the DVP04AD-H is properly grounded , to prevent any electromagnetic noise.
24+ 24-
DC/DC converter
+15V AG -15V
module and terminal of analog input module to system earth point and make system earth point be grounded or connects to machine cover. Note 5: If the noise interference from loaded wire input terminal is significant, please connect a capacitor with 0.1~0.47F 25V for noise filtering. Warning: DO NOT wire to the No function terminal .
3
3.1 Function Specifications
Analog/ Digital (4A/D) module Power supply voltage Analog input channel Analog input range Digital conversion range Resolution Input impedance Overall accuracy Response time Isolation Method Absolute input range Digital data format Average function Self diagnose function Communication mode (RS-485)
STANDARD SPECIFICATIONS
Voltage input Current input 24 VDC(20.4VDC~28.8VDC) ( -15%+20%) 4 channel / each module 10V 20 mA 8000 4000 14 bits(1LSB=1.25 mV) 13 bits (1LSB=5 A) 200 K or above 250 0.5% of full scale of 25(77) 1% of full scale during 0~55 (32~131) 3 ms x channels It has isolation between digital area and analog area. There is no isolation among channels. 15 V 32 mA 2's complementary of 16-bit, 13 Significant Bits Yes (CR#2~CR#5 can be set and setting range is K1~K4096) Upper and lower bound detection / channels Either in ASCII or in RTU mode, communication rate can be 4800 /9600 /19200 /38400 /57600 /115200. Communication format of ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1). Communication format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1). Can't use RS-485 if the connection to PLC MPU is in series. If DVP04AD-H modules are connected to MPU, the modules are numbered from 0 - 7. 0 is the closest and 7 is the furthest to the MPU. 8 modules is the max and they do not occupy any digital I/O points of the MPU. Power Specification 24 VDC(20.4VDC~28.8VDC) ( -15%~+10%), 2W, supply from external power Environment Condition Follow the DVP-PLC MPU All places between terminals and ground comply with the spec.
DVP04AD-H analog signal input module RS-485 CR Parameter Latched Register name No. address #13 H 400D R Present value of CH2 input signal #14 H 400E R Present value of CH3 input signal #15 H 400F R Present value of CH4 input signal #16 ~ #17 #18 H 4012 R/W To adjust OFFSET value of CH1 #19 H 4013 R/W To adjust OFFSET value of CH2 #20 H 4014 R/W To adjust OFFSET value of CH3 #21 H 4015 R/W To adjust OFFSET value of CH4 #22 ~ #23 #24 H 4018 R/W To adjust GAIN value of CH1 #25 H 4019 R/W To adjust GAIN value of CH2 #26 H 401A R/W To adjust GAIN value of CH3 #27 H 401B R/W To adjust GAIN value of CH4 #28 ~ #29 #30 H 401E R Error status
Explanation b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Display the present value of CH3~CH4 input signal Reserved
Offset setting of CH1~CH4. Factory setting is K0 and unit is LSB. Voltage input: setting range is K-4000 ~K4000 Current input: setting range is K-4000 ~K4000
Reserved
GAIN setting of CH1~CH4. Factory setting is K4000 and unit is LSB. Voltage input: setting range is K-3200 ~K16000. Current input: setting range is K-3200 ~K10400.
2
2.1
INTRODUCTION
Model Explanation and Peripherals
Thank you for choosing DELTA's PLC DVP Series. The analog input module receives external 4-point analog signal input (voltage or current) and converts it into 14 bits digital signal. The analog input module of DVP04AD-H series can read/write the data of analog input module by using instructions FROM / TO via DVP-PLC EH Series MPU program. There are 49 CR (Control Register, each register has 16-bit) in each module. Software version of DVP04AD-H analog input module can be updated via RS-485 communication. Users can select input from voltage or current via wiring. Voltage input range is 10V DC (resolution is 1.25 mV). Current input range is 20 mA (resolution is 5 A). Nameplate Explanation
Model Name Input power supply spec. Analog input/output module spec. Barcode
VX.XX
Reserved The data register used to save all error status. Please refer to fault code chart for details. #31 H 401F R/W Communication Setting RS-485 communication address. Setting range is 01~255 and factory setting address setting is K1 #32 H 4020 R/W Communication baud It is used to set communication baud rate (4800, 9600, 19200, 38400, 57600, rate setting 115200bps). Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1). Communication format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1). b0: 4800 bps (bit/sec). b1: 9600 bps (bit/sec). (factory setting) b2: 19200 bps (bit/sec). b3: 38400 bps (bit/sec). b4: 57600 bps (bit/sec). b5: 115200 bps (bit/sec). b6-b13: reserved. b14: exchange low and high byte of CRC check code (only for RTU mode) b15: ASCII / RTU mode selection #33 H 4021 R/W Reset to factory b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 setting and set Reserved CH4 CH3 CH2 CH1 characteristics Factory setting is H0000. adjustable priority Give CH1 setting for example: 1. When b0=0, user can set OFFSET and GAIN value of CH1 (CR#18, CR#24). When b0=1, inhibit user to adjust OFFSET and GAIN value of CH1 (CR#18, CR#24). 2. b1 means if characteristic register is latched. b1=0 (factory setting, latched), b1=1 (not latched). 3. When b2 is set to 1, all settings will reset to factory setting. #34 H 4022 R Software version It is hexadecimal to display software version. For example: H 010A means 1.0A. #35~#48 System used means latched. means not latched. R means can read data by using FROM instruction or RS-485. W means can write data by using TO instruction or RS-485. LSB (Least Significant Bit): 1. Voltage input: 1LSB=10V/8000=2.5mV. 2. Current input: 1LSB=20mA/4000=5A.
20.4VDC ~ 28.8VDC -10V ~ +10V or -20mA ~+20mA 1.25mV or 5 A 04AD-H0T 4120001
Model Explanation
Model Serial Number
Connect to DVP-PLC MPU in series
3.2
Other Specification
Product Series Input+O utput point S: for SS series MPU P: for EP series MPU H: for EH ser ies MPU Production week Production year (2004) Production place (Taoyuan) Production Model
Max. Rated Consuming Power Environment Condition Spec. of Prevent Static Electricity
Model type AD: Analog input module DA: Analog output module PT: Platinum temperatur e sensors(PT-100) TC: Thermocouple sensor s(Type J/K) XA: A/D , D/A Functions RT: Resistor Thermocouple HC: High speed count input module PU: single axis positioning unit
4
DVP04AD-H analog signal input module RS-485 CR Parameter Latched Register name No. address #0 H 4000 R Model type #1 H 4001 R/W Input mode setting
CR (Control Register)
Explanation b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
2.2
Product Profile and Outline
System used. DVP04AD-H model code =H 400 Reserved CH4 CH3 CH2 Input mode setting: factory setting is H0000. Mode 0: input voltage mode (-10V~+10V). Mode 1: input voltage mode (-6V~+10V). Mode 2: input current mode (-12mA~+20mA) Mode 3: input current mode (-20mA~+20mA) Mode 4: none use.
CH1
Unit: mm 1. DIN rail track (35mm) 2. Mounting hole for wire to connect extension unit/extension module 3. Model name 4. Indicator for power, error and run status 5. DIN rail clip 6. Terminals 7. Mounting hole 8. Terminal layout 9. Mounting port to connect extension unit/extension module
#2 #3 #4 #5 #6 #7 #8 #9
H 4002 H 4003 H 4004 H 4005 H 4006 H 4007 H 4008 H 4009

R/W R/W R/W R/W R R R R R
CH1 average times CH2 average times CH3 average times CH4 average times average value of CH1 input signal average value of CH2 input signal average value of CH3 input signal average value of CH4 input signal present value of CH1 input signal
The number of readings used for calculating "average" temperature on channels CH1~CH4. Setting range is K1~K4096 and factory setting is K10.
Display average value of CH1~CH4 input signal
#10 ~ #11 #12 H 400C
Reserved Display present value of CH1~CH2 input signal
Explanation: 1. CR#0: The content of CR#0 is model type, user can read the data from program to know if there is extension module. 2. CR#1: CR#1 is used to set 4 internal channels working mode of analog input module. Every channel has four modes to set and can be set individually. For example: if setting CH1 to mode 0 (b2~b0=000), CH2 to mode 1(b5~b3=001), CH3: mode2 (b8~b6=010), CH4: mode 3(b11~b9=011). It needs to set CR#1 to H0688 and the upper bit (b12~b15) will reserved. The factory setting of CR#1 is H0000. 3. CR#2 ~ CR#5: it is used to set average times of CH1~CH4. Setting range is K1~K4096 and factory setting is K10. 4. CR#6 to CR#9 are the average value that calculates according to the value that is set in CR#2~CR#5 (average time of CH1~CH4 input signal). For example, if CR#2 (the average times of CH1) is 10, it will calculate the average of CH1 input signal every 10 times. 5. CR#10, CR#11, CR#16, CR#17, CR#22, CR#23, CR#28, CR#29 reserved. 6. CR#12 ~ CR#15: display present value of CH1~CH4 input signal. 7. CR #18~ CR #21: the content is the value of adjusting OFFSET value of CH1~CH4 if analog input voltage or current is 0 after it transfers from analog to digital. Voltage setting range: -5V~+5V(-4000LSB~+4000LSB). Current setting range: -20mA~+20mA (-4000LSB~+4000LSB). 8. CR #24~ CR #27: means analog input voltage or current when conversion value from analog signal to digital is 4000. Voltage setting range: -4V~+20V(-3200LSB~+16000LSB). Current setting range: -16mA~+52mA(-3200LSB ~+10400LSB). But please be noticed GAIN VALUE - OFFSET VALUE = +800LSB~+12000LSB (voltage) or +800LSB~+6400LSB (current). When this value under this range, the resolution of the input signal will be thin and the variation of value will be larger. When this value exceeds this range, the resolution of input signal will be thick and the variation of value will be smaller. 9. CR#30 is the fault code. Please refer to the chart below. Fault description Content b15~b8 b7 b6 b5 b4 b3 b2 b1 b0 Power source abnormal K1(H1) 00000001 Analog input value error K2(H2) 00000010 Setting mode error K4(H4) 00000100 Offset/Gain error K8(H8) 00001000 Reserved Hardware malfunction K16(H10) 00010000 Digital range error K32(H20) 00100000 Average times setting error K64(H40) 01000000 Instruction error K128(H80) 10000000 Note: Each fault code will have corresponding bit (b0~b7). Two or more faults may happen at the same time. 0 means normal and 1 means having fault.
10. CR#31: it is used to set RS-485 communication address. Setting range is 01~255 and factory setting is K1. 11. CR#32 is used to set RS-485 communication baud rate: 4800, 9600, 19200, 38400, 57600, 115200 bps. b0: 4800bps. b1: 9600bps. (factory setting) b2: 19200bps. b3: 38400 bps. b4: 57600 bps. b5: 115200 bps. b6-b13: reserved. b14: exchange low and high byte of CRC check code. (only for RTU mode) b15=0: ASCII mode. b15=1: RTU mode. Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1). Communication format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1). 12. CR#33 is used to set the internal function priority, such as characteristic register. Output latched function will save output setting in the inner memory before power loss. 13. CR#34: software version. 14. CR#35~ CR#48: system used. 15. The corresponding parameters address H4000~H4030 of CR#0~CR#48 are provided for user to read/write data through RS-485. A. Communication baud rate: 4800, 9600, 19200, 38400, 57600, 115200 bps. B. Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1). Communication format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1). C. Function code: 03H--read data from register. 06H--write one WORD into register. 10H--write multiple WORD into registers.
M1002 TO TO X0 TO TO K0 K0 K19 K25 K400 K3600 K1 K1 K0 K0 K1 K33 H18 H0 K1 K1
Writing H18 to CR#1 of analog input mode no. 0 and set CH2 to mode 3 (current input: -20 mA ~ +20mA) Writing H0 to CR#33 and allow to adjust characteristics of CH4. When X0 switches from Off to On, K400LSB of OFFSET value will be wrote in CR#19 and K3600LSB of GAIN value will be wrote in CR#25.
The instruction will be executed when X0=On. The instruction won't be executed when X0=Off and the content of previous reading data won't change. X0 FROM K0 K24 D0 K2
API
79
D
TO
P Word device
K H KnX KnY KnM KnS T C
Special module CR data write in
D E F
Applicable model ES EP EH
Bit device
X m1 m2 S n Y M S
6
Lamp display: 1. 2.
INITIAL PLC START-UP
When power is on, POWER LED will be lit and ERROR LED will be lit for 0.5 second. Normal run: POWER LED should be lit and ERROR LED should turn off. When power supply is lower than 19.5V, ERROR LED will blink continuously till the power supply goes higher than 19.5V. 3. When it connects to PLC MPU in series, RUN LED on MPU will be lit and A/D LED or D/A LED should blink. 4. After receiving the first RS-485 instruction during controlling by RS-485, A/D LED or D/A LED should blink. 5. After converting, ERROR LED should blink if input or output exceeds upper bound or lower than lower bound. Example: M1000 FROM K0 D0 K0 K1
M1002 = H400 D0 TO TO = H400 D0 FROM END K0 K0 K0 K1 K2 K6 H3030 K32 D20 K1 K2 K4
16-bit instruction (9 STEPS) Continuous Pulse TO TOP execution execution
5
ADJUST A/D CONVERSION CHARACTERISTIC CURVE
5.1 Adjust A/D Conversion Characteristic Curve
Voltage input mode
+8000
32-bit instruction (17 STEPS) Note: The usage range of operand m1 is 0~7. Continuous Pulse DTOP The usage range of operand m2: ES/EP: 0-48, DTO execution execution EH: 0-254. Flag: When M1083=On, it allows The usage range of operand n: ES/EP: n= to insert interrupt during 1~(49-m2), EH: 1~(255-m2). FROM/TO. For ES series, it doesn't support pulse Refer to following for detail. execution instruction (TOP, DTOP) : the number of special module. of special module that will be wrote in. data number to write in one time. : the number of CR (Control Register) : the data to write in CR. : the
mode 0
Mode 0 of CR#1 GAIN=5V (4000LSB), OFFSET=0V (0LSB)
mode 1
Command Explanation
Digital output
+4000
0 -10V -6V
Mode 1 of CR#1 GAIN=6V (4800LSB), OFFSET=2V (1600LSB) GAIN: Voltage input value when digital output is 4000. Setting range is 5V 6V -4V~+20V (-3200LSB~ +16000LSB) 2V 10V OFFSET: Voltage input value when digital OFFSET GAIN output is 0. -4000 Setting range: -5V~+5V (-4000LSB ~ +4000LSB) GAINOFFSET: Setting range is +1V~+15V (+800LSB~ +12000LSB) -8000 Voltage input
DVP-series PLC uses this instruction to write data into CR of special module. : When assigning bit operand, K1~K4 can be used for 16-bit and K5~K8 can be used for 32-bit.
Program Example
Using 32-bit instruction DTO, program will write D11 and D10 into CR#3 and CR#2 of special module#0. It only writes a group of data in one time (n=1). The instruction will be executed when X0=On and it won't be executed when X0=Off. The data that wrote in previous won't have any change. X0 DTO K0 K2 D0 K1 The rule of instruction operand: m1: arrangement number of special module. The number of special module that connects to PLC MPU. The numbering order of special module from the near to the distant of MPU is from 0 to 7. The maximum is 8 special modules and won't occupy I/O point. m2: the number of CR. Built in 16-bit of 49 groups memory of special module is called CR (Control Register). The number of CR uses decimal digital (#0~#48). All running status and setting values of special module has included. If using FROM/TO instruction, the unit of read/write of CR is one number for one time. If using DFROM/DTO instruction, the unit of read/write of CR is two numbers in one time. Upper 16-bit Lower 16-bit
Current input mode:
+4000
mode 3
Mode 2 of CR#1 GAIN = 20mA (4000LSB), OFFSET=4mA (800LSB).
Footnote
Digital output
-20mA -12mA 0 4mA OFFSET
Mode 3 of CR#1 GAIN = 20mA (4000LSB), mode 2 OFFSET=0mA (0LSB). Current input value when digital output is +4000. Setting range is -20 mA~+20 mA (-4000LSB ~ +4000LSB ) OFFSET: Current input value when digital output value is 0. Setting range is-16 mA ~+52 mA (-3200LSB ~ +10400LSB) GAINOFFSET: Setting range is +4mA ~ +32mA (800LSB~ +6400LSB) GAIN:
Explanation: Read the data of model type from extension module K0 and distinguish if the data is H400 (DVP04AD-H model type). If the model type is DVP04AD-H, M11 is on and the setting input mode is (CH1, CH3)= mode 0, (CH2, CH4)= mode 3. Set the number of times for average of CH1 and CH2 are K32. Read the input signal average value of CH1~CH4 (4 data) and saved into D20~D23.
20mA GAIN
-4000
current input
Using charts above to adjust A/D conversion characteristic curve of voltage input mode and current input mode. Users can adjust conversion characteristic curve by changing OFFSET values (CR#18~CR#21) and GAIN values (CR#24~CR#27) depend on application. LSB(Least Significant Bit): 1. voltage input: 1LSB=10V/8000=1.25mV. 2. current input: 1LSB=20mA/4000=5A.
7
API
RELATED INSTRUCTIONS EXPLANATION
78
D
FROM
P
Read special module CR data
Applicable model ES EP EH
CR #10 CR #9 Specified CR number (Access16-bit if n=2, or 32-bit if n=1. Same controlled registers are accessed).
Specified device D0 D1 D2 D3 D4 D5 Specified CR CR #5 CR #6 CR #7 CR #8 CR #9 CR #10 Specified device Specified CR D0 D1 D2 D3 D4 D5 CR #5 CR #6 CR #7 CR #8 CR #9 CR #10
5.2. Program Example for Adjusting A/D Conversion Characteristics Curve
Example 1: setting OFFSET value of CH1 to 0V(=K0LSB) and GAIN value of CH1 to 2.5V(=K2000LSB).
M1002 TO TO X0 TO TO K0 K0 K18 K24 K0 K2000 K1 K1 K0 K0 K1 K33 H0 H0 K1 K1
Writing H0 to CR#1 of analog input module no. 0 and set CH1 to mode 0 (voltage input -10V~+10V) Writing H1 to CR#33 and allow to adjust characters of CH1~CH4. When X0 switches from Off to On, K0LSB of OFFSET value will be wrote in CR#18 and K2000LSB of GAIN value will be wrote in CR#24.
Bit device Word device 16-bit instruction (9 STEPS) X Y M S K H KnX KnY KnM KnS T C D E F Continuous Pulse FROM FROMP m1 execution execution m2 D 32-bit instruction (17 STEPS) n Continuous Pulse DFROM DFROMP Note: The usage range of operand m1 is 0~7. execution execution The usage range of operand m2: ES/EP: Flag: When M1083=On, it allows to 0-48, EH: 0-254. insert interrupt during The usage range of operand n: ES/EP: n= FROM/TO. 1~(49-m2), EH: 1~(255-m2). Refer to following for detail. ES series model doesn't support pulse execution instruction (FROMP, DFROMP).
Command Explanation
In ES series models, flag M1083 is not provided. When FROM/TO instruction is executed, all interrupts (including external or internal interrupt subroutines) will be disabled. All interrupts will be executed after completing FROM/TO instruction. Besides, FROM/TO instruction also can be executed in the interrupt subroutine. The function of the flag M1083 (FROM/TO mode exchange) provided in EP/EH series models: a. When M1083=Off, all interrupts (including external or internal interrupt subroutines) will be disabled when FROM/TO instruction is executed. The Interrupts will resumed after FROM/TO instruction complete. Please be advised FROM/TO instruction can be executed in the interrupt subroutine. When M1083=On, if an interrupt enable occurs while FROM/TO instruction are executing, the interrupt FROM/TO instruction will be blocked till the requested interrupt finish. Unlike M1080 off situation, FROM/TO instruction cannot be executed in the interrupt subroutine.
16-bit command when n=6
32-bit command when n=3
Example 2: setting OFFSET value of CH2 to 2mA(=K400 LSB) and GAIN value of CH2 to 18 mA (=K3600LSB)
: the number for special module. : the number of CR (Control Register) of special module that will be read. : the location to save reading data. : the data number of reading one time. DVP-series PLC uses this instruction to read CR data of special module. : When assigning bit operand, K1~K4 are used for 16-bit and K5~K8 are used for 32-bit. Please refer the footnote below for the calculation of special module number. To read the content of CR#24 of special module#0 to D0 of PLC and to read the content of CR#25 of special module#0 to D1 of PLC. It can read 2 data in one time (n=2).
b.
Program Example


▲Up To Search▲   

 
Price & Availability of DVP04TC-S

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X